Breaker Size Calculator
Determine the correct circuit breaker size.
Last updated 2026-08-21
What Is a Breaker Size Calculator?
A breaker size calculator finds the correct circuit breaker rating for a load based on its wattage, voltage, and whether it runs continuously. It applies the 125% safety margin that code requires for continuous loads, then rounds up to a standard breaker size. This keeps the breaker matched to both the load and the wire.
How It Works
Load current = Watts ÷ Voltage. Continuous loads derate × 1.25. Breaker = next standard size ≥ derated amps.
Example
2,400 W at 120 V continuous: 20 A × 1.25 = 25 A → 25 A breaker.
How to Calculate
- Enter the total load in watts, for example 2,400 W, and the voltage, commonly 120 V.
- Indicate whether the load is continuous, meaning it runs three hours or more at a time.
- The tool converts watts to amps, so 2,400 ÷ 120 gives 20 A, then multiplies by 1.25 for the continuous margin to get 25 A.
- It rounds up to the next standard breaker size, in this case 25 A. Always pair the breaker with the correct wire gauge and verify with an electrician.
Standard breaker sizes
| Standard size | Common use | Typical wire |
|---|---|---|
| 15 A | Lighting, general receptacles | 14 AWG |
| 20 A | Kitchen and counter circuits | 12 AWG |
| 30 A | Dryers, water heaters | 10 AWG |
| 40 A | Ranges, some EV chargers | 8 AWG |
| 50 A | Ranges, welders | 6 AWG |
Sources
Frequently Asked Questions
What is a continuous load?
A load expected to run 3+ hours, like lighting and some appliances — NEC requires a 125% safety margin.
What are standard breaker sizes?
15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, and 100 A.
Can I use the next size up?
No — the breaker must be rated for the wire, not just the load. Always confirm with a licensed electrician.
Estimate the cost with the Electrical Cost Calculator or browse Electrical Calculators